Heat pump in a 1930s semi in the UK — does it work out once the grant is in? Heat Pump

Gas combi from 2011, about 14,000 kWh of gas a year, cavity walls filled and loft at roughly 270 mm, but the ground floor is suspended timber and noticeably draughty. Two quotes in, both in the mid-teens of thousands before any grant. I keep being told the running cost is roughly a wash against gas at current prices and that the real case is the grant plus never replacing a boiler again. What did your bills actually do?

11 answers Share
Report

Answering anonymously — a moderator will review it first.

  • @zigbee_zoe · 7h ago · 3 replies

    Bills first: mine went from roughly £1,100 of gas to roughly £950 of electricity for heating, on a house slightly tighter than yours, running a seasonal efficiency around 3.2. That's not the dramatic win I'd been promised. What made it work anyway was the Boiler Upgrade Scheme — £7,500 towards an air source unit, applied for by the installer rather than by you. There's also a temporary uplift to £9,000 running from 21 July 2026 for off-gas-grid oil and LPG homes, which won't apply to you on mains gas.

    176
    Share
    Reply

    Answering anonymously — a moderator will review it first.

    Report
    • @knobandtube_nan · 23h ago

      £950 against £1,100 is roughly what my installer implied and roughly what I feared.

      44
      Share
      Reply

      Answering anonymously — a moderator will review it first.

      Report
    • @zigbee_zoe · 20h ago

      The ratio between the electricity unit rate and the gas unit rate is the whole game in the UK. Watch that number harder than any spec sheet.

      26
      Share
      Reply

      Answering anonymously — a moderator will review it first.

      Report
  • @probe_to_ground · 10h ago · 2 replies

    Your suspended timber floor is the actual project here. A heat pump wants to run at a low flow temperature, and a draughty floor void keeps room heat loss high, which forces the flow temperature up, which drags the efficiency down. Insulating between the joists is unglamorous and it's the difference between a real-world COP of 2.6 and 3.4 on the same equipment.

    114
    Share
    Reply

    Answering anonymously — a moderator will review it first.

    Report
    • @cadence_cam · 2d ago

      Seconding this. The best-performing installs I know of are boring houses with good airtightness, not clever kit in leaky ones.

      37
      Share
      Reply

      Answering anonymously — a moderator will review it first.

      Report
  • @day_rate_dee · 18h ago

    Get the heat loss calculation as a document and read it properly. If the installer sized the unit off floor area, or off the output of your existing boiler, walk away. Oversized units cycle, cycle badly, and then their owners write posts about how heat pumps are noisy and expensive.

    79
    Share
    Reply

    Answering anonymously — a moderator will review it first.

    Report
  • @solder_sundays · 23h ago

    Ask specifically what flow temperature the design assumes and what radiator changes are included. A quote that assumes 45°C with your existing radiators and no upgrades is either optimistic or you have unusually generous rads for a 1930s semi.

    56
    Share
    Reply

    Answering anonymously — a moderator will review it first.

    Report
  • @mulch_marta · 3h ago · 2 replies

    Slightly against the grain: I'd keep the 2011 combi until it actually dies. It's fifteen years old, not thirty. Doing the floor and the airtightness work now, with the boiler still in place, means the heat pump quote in three years will be smaller and better designed. Grants change, but so do install prices and so does the kit.

    38
    Share
    Reply

    Answering anonymously — a moderator will review it first.

    Report
    • @zigbee_zoe · 3d ago

      Reasonable, with the caveat that grant schemes are political and the current one has an end date attached. It's a gamble in both directions rather than a safe wait.

      24
      Share
      Reply

      Answering anonymously — a moderator will review it first.

      Report
  • @lowtech_lior · 3h ago

    Whatever you do, check the noise limits and where the unit would sit relative to your neighbour's windows. That's the complaint that ends up in a formal letter rather than a chat over the fence.

    22
    Share
    Reply

    Answering anonymously — a moderator will review it first.

    Report
  • @root_rot_ronan · 2d ago

    The tariff matters as much as the pump. Moving to a time-of-use tariff with a cheap overnight rate, plus decent controls, shifted my numbers more than any efficiency tweak I made to the system itself.